Quick Details

  • Place of Origin: Guangdong, China (Mainland)
  • Brand Name: Asenware
  • Model Number: AW-AFP2166
  • Executive standard: GB19880-250
  • Certificates: CE.ISO9001
  • Working Environment: Construction buildings.home secutiry
  • Nature: conventional
  • Product Name: 2 Loops 4 Zone Conventional Fire Alarm Control Panel (AW-CFP2166)
  • Voltage: 24V DC
  • Circus Bus: 2 bus system
  • Weight: 7kg
  • Color: black white
  • capacity: 20 detectors one zone

Packaging & Delivery

Packaging Details use carton to pack conventional fire alarm system well
Delivery Time 3 to 5 days

Introduction

1 ,AW-CFP2166 series conventional fire alarm panel is designed based on  EN54 part 2&4 standard.

2, It is modularized design, the panel can expend from 1 zone to 32  zones easily.

3, It has 2 level control mode by a lock.

4, It has 24VDC and 5VDC power supply output.

5, It has FIRE and FAULT signal output.

6, It has 2 general sounders output.

7, Each zone has 1 circuit detectors input.

8, Each zone can be disable by a button.

9, It has RESET button to reset the panel.

10, It has SILENCE button to stop BUZZER and SOUNDERS.

11, It has EVACUATE button to start a manual fire alarm immediately.

12, It has an optional GSM module for fire alarm by SMS.

13, It is economic, user-friendly and easy maintenance.

Parameters

ITEM1 Zone panel2 Zone panel4-8 Zone panel4-32 Zone panel
Model No.AW-CFP2166-01AW-CFP2166-02AW-CFP2166-04-08AW-CFP2166-04-16
Power specification    
Mains supply voltage110VAC or 240VAC   
Internal power supply27.2VDC   
Total output current limited500mA @ 240VAC 3A @ 240VAC 
Main supply monitor for faultYes   
Battery protection for low voltageYes   
Batteries (default configuration)12V2AH*2   
Detector circuit specification    
Number of circuit124-84-32
Line fault monitor for open circuitYes   
Line fault monitor for short circuitYes   
Line fault monitor for detector removalYes, if End of Line Monitor Unit fitted in place of End of Line Resistor   
End of Line device6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)   
Detector continuity diodesSilicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault)   
Call point resistor value470 to 680 Ω, 0.225 or 0.5 watt   
Maximum number of smoke/heat detectors per zone20 (based on a total detector current of 2mA, each detector consuming 100μA).Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts.   
Maximum number of manual call points per zoneNo limit   
Sounder circuit specification    
Number of general circuits2   
End of line resistor value6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)   
Line fault monitor for open circuitYes   
Line fault monitor for short circuitYes   
Outputs fused AT400mA   
Maximum number of bells @ 20mA of each Sounder output20   
Fuses    
Battery fuse1.5A F 20mm   
Sounder outputs500mA F 20mm   
Fire output    
Output typeNC and NO relay   
Maximum current100mA   
Connection block    
Largest acceptable conductor size2.5mm2   
Smallest acceptable conductor size0.75mm2   
Size and weight    
Dimensions(mm)272X200X70320X231X90395X502X124362X565X124
Weight (without batteries)4kg5kg7kg8kg
Weight (with batteries)5.8kg6.8kg19.6kg12.5kg

 

 

 

 

 

Transaction History of the Supplier

Below is the information about the supplier's transactions conducted via Alibaba.com. If you require further details regarding the transaction data, please contact the supplier directly.

Transaction Overview

Transactions

Transaction Details

This supplier has completedtransactions with buyers from .

Shipping Destination
Transaction Value
Transaction Date
Email to this supplier
Trade Assurance
China (Mainland)
Transaction Level:
Supplier Assessments:
20 Transactions 30,000+
The supplier’s transactions conduted via Alibaba.com in the past 6 months.
The supplier supports Trade Assurance – A free service that protects your orders from payment to delivery.
Supplier's Trade Assurance Limit: US $69,000
Learn More